Viessmann · Boiler troubleshooting

Digital inputs DE1 to DE3 wiring and function options

Vitodens 200-W B2HB

What is going on

External contacts must be floating. Follow the safety category II spacing: 8.0 mm air and creep path, or 2.0 mm insulation thickness to live parts. Each input can be set to one function.

Check in this order

  1. Use only floating (potential-free) external contacts.
  2. Keep 8.0 mm air and creep path, or 2.0 mm insulation, to live parts.
  3. Choose the function for each input with coding addresses 3A (DE1), 3B (DE2) and 3C (DE3) in the General group.
  4. Functions available external heating program changeover per heating circuit, external blocking, external blocking with fault input, external demand with minimum boiler water temperature, fault message input, brief DHW recirculation pump operation, and zone circuit pump operation.

Applies to: Internal extension EA1

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB service instructions, p. 88. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.