Viessmann · Boiler troubleshooting

CSD-1 fixed high limit field test (simulation #1)

Vitodens 200-W B2HB

What is going on

Field test of the fixed high limit where required by law. Viessmann is not responsible for damage caused by overheating the system during this test.

Check in this order

  1. Close the boiler valve and jumper across the flow switch.
  2. On B2HB models, set coding address 06 to maximum on the coding card.
  3. Run the boiler at high fire. It will shut down from the coding card but the boiler temperature should keep rising until the fixed high limit trips.
  4. Once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down safely.

Applies to: Vitodens 200-W B2HB, all models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.