Weil-McLain · Boiler troubleshooting
Direct exhaust sidewall termination steps
What is going on
Use a coupling that butts against the outside wall plate. Choose the left-side configuration unless it fails minimum clearance to grade or snow line, then use the raised right-side (snorkel) configuration. Do not terminate next to the wall, under eaves, parapets, balconies or decks.
Check in this order
- Set the termination coupling against the outside wall plate.
- If clearance to grade or snow line fails, use the raised snorkel configuration with an elbow.
- Prepare wall penetrations before installing vent piping.
- Attach external pipe and fittings per termination instructions.
- Support vertical runs on the outside with brackets.
- Install vent piping from boiler to termination, with hanger support within 6 in of any upturn.
- Connect vent piping at the boiler per manual instructions.
Applies to: Sidewall direct exhaust
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 31, 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.