Viessmann · Boiler troubleshooting

Flow switch / flow sensor test

Vitodens 200-WB2HA

What is going on

The boiler has two flow sensing devices. If flow is too low, they shut the burner down and block restart until flow is restored.

Check in this order

  1. Throttle the water flow to or from the boiler.
  2. Confirm the boiler shuts down once flow drops below its safe operating set point.
  3. Restore flow and confirm the boiler restarts.

Applies to: Vitodens 200-W B2HA 112/150/399/530

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.