Viessmann · Boiler troubleshooting
Removing top panels and upper frame for burner access
What is going on
Panel removal needed before burner work. Screw count differs by size. Upper frame profiles must come off to remove the burner.
Check in this order
- Close the gas shut-off valve and isolate power. Let the system cool.
- CA3B 2.5 to 4.0: remove the 4 screws from the right side of the top panels.
- CA3B 5.0 and 6.0: remove the 6 screws from the right side of the top panels.
- Lift off the top right side panels, then slide the top panels to the right and remove them.
- Lift off the top left side panels.
- Remove the nut and bolt from each side of the lower portion of the upper frame profiles.
- Remove the upper frame profiles.
- After service, reinstall the upper frame profiles and panels.
Applies to: Vitocrossal 300 CA3B 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 50. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.