Viessmann · Boiler troubleshooting

Check sight glass, insulation blanket and mixing valve

Vitorond 200 VD2

What is going on

Check the insulation fit and control operation.

Likely causes

  • Leaking mixing valve O-rings

Check in this order

  1. Make sure the insulation blanket fits properly.
  2. Remove the motorized arm from the mixing valve and check the motor moves freely.
  3. If the mixing valve is not watertight, replace the O-rings.
  4. Snap the motorized arm back into place.

Applies to: All VD2 sizes 320 to 1080

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.