Weil-McLain · Boiler troubleshooting
Multi-boiler RS485 wiring
What is going on
Boilers communicate over a shielded 3-wire RS485 bus. The Unity 2.0 boiler must be the Master.
Check in this order
- Use shielded 3-wire cable, no longer than 1,000 feet.
- Connect Boiler-to-Boiler OUT (JP4 GND, B2, A2) on one boiler to Boiler-to-Boiler IN (JP4 GND, B3, A3) on the next.
- Continue until all boilers are interconnected.
- Install the drain line to proper ground on the Master boiler only. Do not ground on both the Master and the final boiler.
- Do not return the last boiler's wires to the Master's A3/B3/GND ports. This creates a communication loop.
Applies to: Evergreen 110/155/220/299/300/399 multi-boiler installs
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 55. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.