Oil burner will not fire (steam boiler)

Weil-McLain SGO Series 4

What is going on

Basic checks before calling it a burner problem. Do not keep hitting the reset on the primary control.

Likely causes

  • Boiler service switch off, fuse blown or breaker tripped
  • Thermostat set below room temperature
  • Oil valves closed
  • No water showing in the gauge glass (low water cutoff holding the burner off)
  • Oil tank too low to feed the burner

Check in this order

  1. Look in the combustion chamber first. If there is oil sitting in the chamber, do not fire the burner until it is cleaned out.
  2. Check power service switch, fuse and breaker.
  3. Turn the thermostat up above room temperature.
  4. Make sure the oil valves are open and there is enough oil in the tank.
  5. Check that water is visible in the gauge glass. If not, fill to the water line marked on the jacket.
  6. Press the reset on the burner primary control one time only. Each extra press pumps more oil into the chamber and creates a fire hazard.
  7. Still no fire move on to burner diagnostics (pump pressure, nozzle, ignition, cad cell) per the burner manual.

Applies to: SGO-3 to SGO-9 oil-fired steam boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Start-up p.6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.