Connect two or more remote controls

Vitotronic 200

What is going on

Use the KM-BUS Expansion Module or a field-supplied junction box when connecting two or more remote controls.

Check in this order

  1. If no other BUS participants are connected, plug each remote control's connector into the KM-BUS Expansion Module.
  2. If other BUS participants are also connected, wire all of them through a field-supplied junction box.
  3. Keep the total cable length to the control unit at max. 164 ft / 50 m.
  4. Keep each remote control's cable run at max. 50 ft / 15 m from the junction box.

Applies to: Vitotronic 200 KW2 with multiple Vitotrol remote controls

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 service instructions, p. 78. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.