Condensate drain connection

NFB

What is going on

Condensate must drain from the 3/4 in condensate outlet, and the trap must be primed with water.

Check in this order

  1. Connect the drain pipe to the 3/4 in NPT condensate outlet at the bottom of the unit.
  2. Pour water into the exhaust connection to fill the condensate trap.
  3. Drain the pipe end to a laundry tub or floor drain, or use an allowed external drain, neutralizer or condensate pump.
  4. Do not submerge the pipe end in water.

Applies to: NFB-301C/399C

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NFB-C quick installation guide, p. 2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.