Weil-McLain · Boiler troubleshooting
Check inhibitor and antifreeze levels yearly
What is going on
Water chemistry and antifreeze strength change over time, so test them at least once a year.
Likely causes
- Inhibitor level drops over time.
- Antifreeze concentration drops if a fitting or seal leaks and only water is lost.
Check in this order
- Test the pH of a system water sample. It must be between 7.0 and 8.5.
- Use the Sentinel inhibitor test kit to check inhibitor concentration.
- If pH is out of range or the inhibitor is low, add inhibitor or treat the system as the manual directs.
- Test antifreeze concentration. If it is low, add antifreeze or drain and refill with the correct mix.
- Recheck inhibitor level after any adjustments.
Applies to: Systems with inhibitor or antifreeze
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 86. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.