Check inhibitor and antifreeze levels yearly

SVF Series 1

What is going on

Water chemistry and antifreeze strength change over time, so test them at least once a year.

Likely causes

  • Inhibitor level drops over time.
  • Antifreeze concentration drops if a fitting or seal leaks and only water is lost.

Check in this order

  1. Test the pH of a system water sample. It must be between 7.0 and 8.5.
  2. Use the Sentinel inhibitor test kit to check inhibitor concentration.
  3. If pH is out of range or the inhibitor is low, add inhibitor or treat the system as the manual directs.
  4. Test antifreeze concentration. If it is low, add antifreeze or drain and refill with the correct mix.
  5. Recheck inhibitor level after any adjustments.

Applies to: Systems with inhibitor or antifreeze

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 86. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.