Weil-McLain · Boiler troubleshooting
Close clearance install: burner off on manual reset temperature switch
What is going on
In an alcove or closet install with the close clearance kit, a manual reset temperature switch near the ceiling is wired in series with the thermostat. If it trips, the boiler gets no call for heat.
Likely causes
- Manual reset temperature switch above the boiler tripped from heat build-up in the enclosure
- Missing or blocked combustion/ventilation openings
- Burner combustion off
Check in this order
- Power off before working in the burner or junction box.
- Find the manual reset temperature switch near the top of the enclosure and reset it.
- Find out why it tripped check both combustion/ventilation openings (sized 140 sq. in. per 1 GPH input, one near the top and one near the bottom).
- Check the barometric damper is installed 18 to 20 in. from the boiler in the breeching.
- Make sure the jacket cap is in place.
- Set combustion with an analyzer 13% CO2 or lower, zero smoke, overfire draft -0.01 to -0.02 in. w.c.
Applies to: WGO-2 to WGO-9 oil-fired water boilers with close clearance kit 386-500-050
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain WGO Series 4 Water Boiler Manual 550-142-331/0225, Close clearance installation p.31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.