Weil-McLain · Boiler troubleshooting

Close clearance install: burner off on manual reset temperature switch

Weil-McLain WGO Series 4

What is going on

In an alcove or closet install with the close clearance kit, a manual reset temperature switch near the ceiling is wired in series with the thermostat. If it trips, the boiler gets no call for heat.

Likely causes

  • Manual reset temperature switch above the boiler tripped from heat build-up in the enclosure
  • Missing or blocked combustion/ventilation openings
  • Burner combustion off

Check in this order

  1. Power off before working in the burner or junction box.
  2. Find the manual reset temperature switch near the top of the enclosure and reset it.
  3. Find out why it tripped check both combustion/ventilation openings (sized 140 sq. in. per 1 GPH input, one near the top and one near the bottom).
  4. Check the barometric damper is installed 18 to 20 in. from the boiler in the breeching.
  5. Make sure the jacket cap is in place.
  6. Set combustion with an analyzer 13% CO2 or lower, zero smoke, overfire draft -0.01 to -0.02 in. w.c.

Applies to: WGO-2 to WGO-9 oil-fired water boilers with close clearance kit 386-500-050

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain WGO Series 4 Water Boiler Manual 550-142-331/0225, Close clearance installation p.31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.