Weil-McLain · Boiler troubleshooting

Pilot flame signal lost during operation

CGi Series 5

What is going on

During main burner operation the control monitors pilot flame current. If the signal is lost, the boiler re-ignites automatically.

Check in this order

  1. The main valve closes when the pilot flame signal is lost.
  2. The spark generator activates.
  3. The control returns the sequence to the prepurge step to restart ignition.
  4. If the boiler does not light, check for a lockout and follow the ignition fault reset.

Applies to: CGi Series 5 spark-ignited pilot boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 gas-fired water boiler manual, p. 45. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.