Viessmann · Boiler troubleshooting

Combustion air device adaptor wiring (VD2/VD2A/CT3)

Vitotronic 100

What is going on

Connecting the combustion air blower through the adaptor to the control.

Check in this order

  1. Disconnect power to the control and burners.
  2. Mount the combustion air device adaptor (part 7134 563) on the DIN rail inside the connection enclosure, following the adaptor manual.
  3. Remove the jumper between terminals 16 and 17.
  4. Connect BK2 to terminal 16 and BK3 to terminal 17. Do not reverse them.
  5. Wire the blower (120 VAC, max 5 FLA, AWG 14) to the adaptor as shown. The proving switch must be normally open and rated 120 VAC.
  6. Connect 120 VAC power with disconnect and overcurrent protection as required by local codes.

Applies to: Vitocrossal 300 VD2/VD2A/CT3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 installation manual, p. 66. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.