Navien · Boiler troubleshooting

Wiring zone valves (no 24 VAC supplied to valves)

NCB700

What is going on

A 3-zone valve system uses zone valves instead of zone pumps. Zone pump 3 terminal is used for the system pump. Each zone valve has a normally open (NO) and normally closed (NC) contact, with COM as the common.

Likely causes

  • Total zone valve draw over 72 VA needs an external zone valve controller.

Check in this order

  1. Connect zone valves 1 to 3 to their terminals (max 1 A each).
  2. Connect the system pump to the zone pump 3 terminal (max 2.5 A).
  3. Wire the recirculation pump (max 2.5 A) and boiler internal pump as shown.
  4. Set the valve contacts NO means power is supplied when the valve is open; NC means power is supplied when the valve is closed.
  5. Do not use COM as a 24 VAC supply in this layout (it is not used).
  6. If the three zone valves draw more than 72 VA total, install an external zone valve controller.

Applies to: NCB700 boilers with zone valves

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 213. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.