Wiring zone valves (no 24 VAC supplied to valves)
What is going on
A 3-zone valve system uses zone valves instead of zone pumps. Zone pump 3 terminal is used for the system pump. Each zone valve has a normally open (NO) and normally closed (NC) contact, with COM as the common.
Likely causes
- Total zone valve draw over 72 VA needs an external zone valve controller.
Check in this order
- Connect zone valves 1 to 3 to their terminals (max 1 A each).
- Connect the system pump to the zone pump 3 terminal (max 2.5 A).
- Wire the recirculation pump (max 2.5 A) and boiler internal pump as shown.
- Set the valve contacts NO means power is supplied when the valve is open; NC means power is supplied when the valve is closed.
- Do not use COM as a 24 VAC supply in this layout (it is not used).
- If the three zone valves draw more than 72 VA total, install an external zone valve controller.
Applies to: NCB700 boilers with zone valves
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 213. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.