Weil-McLain · Boiler troubleshooting
Sidewall termination clearances
What is going on
A sidewall termination must stay clear of door and window openings, roof overhangs, forced air intakes and other vent exit points. Do not terminate above a door or window or under a deck, since condensate can freeze.
Check in this order
- Keep at least 6 ft from adjacent walls.
- Keep at least 5 ft below any roof overhang.
- Keep at least 3 ft above any forced air intake within 10 ft.
- Keep at least 48 in below or horizontal from any door, window or gravity air inlet.
- Do not terminate above a door or window or under a deck.
- Do not place the termination where plume or condensate will damage shrubs, air conditioners or building surfaces.
Applies to: Direct exhaust sidewall termination
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.