Weil-McLain · Boiler troubleshooting

Sidewall termination clearances

SlimFit Series 3

What is going on

A sidewall termination must stay clear of door and window openings, roof overhangs, forced air intakes and other vent exit points. Do not terminate above a door or window or under a deck, since condensate can freeze.

Check in this order

  1. Keep at least 6 ft from adjacent walls.
  2. Keep at least 5 ft below any roof overhang.
  3. Keep at least 3 ft above any forced air intake within 10 ft.
  4. Keep at least 48 in below or horizontal from any door, window or gravity air inlet.
  5. Do not terminate above a door or window or under a deck.
  6. Do not place the termination where plume or condensate will damage shrubs, air conditioners or building surfaces.

Applies to: Direct exhaust sidewall termination

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.