Viessmann · Boiler troubleshooting
Adjust CO2 at partial load (lower heating output)
What is going on
Check and correct CO2 at lower heating output, then recheck full load.
Check in this order
- Press button D until the service indicator shows 0 (lower heating output).
- Measure CO2 at the flue gas pipe.
- If CO2 must change, unscrew cover cap B and turn adjustment screw A in small steps with a Torx 40.
- Turning clockwise raises CO2; counter-clockwise lowers CO2.
- Record the reading in the maintenance record on page 158.
- Start upper and lower heating output again via the burner control. If values are out of range, repeat both steps.
- Press buttons S E and D together for more than 2 seconds to return the burner to operating mode.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 67. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.