Adjust CO2 at partial load (lower heating output)

Vitocrossal 300 CA3B Dual Fuel

What is going on

Check and correct CO2 at lower heating output, then recheck full load.

Check in this order

  1. Press button D until the service indicator shows 0 (lower heating output).
  2. Measure CO2 at the flue gas pipe.
  3. If CO2 must change, unscrew cover cap B and turn adjustment screw A in small steps with a Torx 40.
  4. Turning clockwise raises CO2; counter-clockwise lowers CO2.
  5. Record the reading in the maintenance record on page 158.
  6. Start upper and lower heating output again via the burner control. If values are out of range, repeat both steps.
  7. Press buttons S E and D together for more than 2 seconds to return the burner to operating mode.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 67. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.