Fill heating system with water

Vitodens 200-W B2HB

What is going on

Flush the system before filling and use potable-quality water. Soften the water if it is harder than 8.77 grains / 150 ppm total dissolved solids. Use only inhibitors or antifreeze made for hot water heating. Do not use automotive silicate antifreeze.

Check in this order

  1. Thoroughly flush the entire heating system before filling.
  2. Confirm all necessary flow check valves are installed and system isolation valves at C and D are open (if installed).
  3. Check the expansion tank precharge against static pressure before filling.
  4. Fill the system at the boiler fill (BF) and bleed air fully from the boiler drain (BD).
  5. If using antifreeze, use 40% for protection to -10°F (-23°C) and follow the manufacturer specifications.
  6. Check the total system frequently when filled with antifreeze.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.