Weil-McLain · Boiler troubleshooting
Convert natural gas boiler to propane
What is going on
Propane conversion needs the correct LP kit and a flue gas analyzer. The gas supply must be shut off and power disconnected before starting. The venturi must not be modified.
Check in this order
- Turn off gas supply, turn off power and let the boiler cool.
- Confirm the propane venturi has a black label marked LP. Do not change or modify the venturi.
- Set the boiler control fuel type to Propane before firing (see tip on fuel type).
- Remove the front door and the air silencer clip, then remove the silencer from the venturi.
- Label all wires, then disconnect the wire harness from the gas valve.
- Loosen the gas pipe swivel nut at the venturi. Use two wrenches, with a pipe wrench on the gas pipe. Loosen the U-bolt if needed.
- Remove the three T20 Torx screws holding the venturi. Replace the O-ring and fiber washer and inspect the blower surface.
- Install the new propane venturi with the new O-ring seated in the blower groove. Fit three new Torx screws and torque to no more than 23 inch-pounds.
- Install the propane orifice into the venturi gas inlet.
- Reconnect the gas pipe with the new fiber washer and tighten the swivel nut with two wrenches.
- Reassemble the silencer and clip and confirm the clip is seated correctly.
- Reconnect the gas valve harness and check all connections for leaks with a bubble test.
- Affix the installer conversion label next to the rating label.
- Set the gas valve course adjustments before first ignition (see setting table).
- Run the full startup with a combustion analyzer and adjust high and low fire.
Applies to: ECO Tec 80/110/150/199 natural gas to propane
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Boiler Manual, p. 19-23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.