Weil-McLain · Boiler troubleshooting

Gas supply for manifolded multiple boilers

SVF Series 1

What is going on

Gas piping setup when several boilers share one supply line.

Likely causes

  • Undersized supply piping causing low pressure at a boiler when others fire

Check in this order

  1. Size the manifold supply piping as for a single boiler.
  2. At each boiler, install a manual shutoff gas valve, a union and a sediment trap at least 3 inches below the tee.
  3. Check that minimum gas pressure at each boiler stays at the required value with all connected appliances firing.

Applies to: Multiple boiler gas manifolds

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.