Gas supply for manifolded multiple boilers
What is going on
Gas piping setup when several boilers share one supply line.
Likely causes
- Undersized supply piping causing low pressure at a boiler when others fire
Check in this order
- Size the manifold supply piping as for a single boiler.
- At each boiler, install a manual shutoff gas valve, a union and a sediment trap at least 3 inches below the tee.
- Check that minimum gas pressure at each boiler stays at the required value with all connected appliances firing.
Applies to: Multiple boiler gas manifolds
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 48. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.