Viessmann · Boiler troubleshooting

Set maximum output

Vitodens 200-W B2HA

What is going on

Limits the maximum heating input through the modulation range. The limit cannot exceed the boiler coding card.

Check in this order

  1. Press OK and the second button at the same time for about 4 seconds.
  2. Select "Service functions".
  3. Select "Maximum output".
  4. Select "Yes" at "Change?".
  5. A value flashes (factory 85 = 100% of rated input).
  6. Select the required value.

Applies to: Vitodens 200-W B2HA 19, 28, 35

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.