Viessmann · Boiler troubleshooting
Check and replace burner refractory and cylinder burner
What is going on
Inspect the refractory ring and cylinder burner assembly.
Check in this order
- Remove the electrode block and ionization electrode B.
- Undo the three retaining clips C and remove the refractory ring D.
- Loosen the four Torx screws and remove the cylinder burner assembly E and assembly gasket F.
- Fit the new cylinder burner assembly and new gasket. Tighten to 31 lb.in. (3.5 Nm).
- Reinstall the refractory ring and clips.
- Reinstall the electrode block and ionization electrode. Tighten to 40 lb.in. (4.5 Nm).
- Check burner gasket A for damage. Generally replace it every 2 years.
Applies to: Vitodens 200-W B2HA 19, 28, 35
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.