Viessmann · Boiler troubleshooting
Boiler control housing and enclosure installation
What is going on
Mount the boiler control housing on the side panel, route the capillaries and boiler sensor, then close up the enclosure panels.
Check in this order
- Remove the two plugs on the back of the control housing with a flathead screwdriver.
- Mount the control housing on the side panel and secure it with the two supplied screws.
- Run the capillaries and boiler temperature sensor through the 22 mm opening in the side panel and push them as far as possible into the sensor well.
- Keep all cabling and capillaries away from high heat sources such as the vent, chimney and supply/return piping.
- Hook the top panel into the side panels, then attach the mid top panels on VD2-500 and larger.
- Secure the rear of the top panels to the side panels and fasten them to the rear panels with B 3.5 x 9.5 sheet metal screws.
- Fasten the brackets to the rear panel with sheet metal screws.
- Mount the Vitorond 200 nameplate to the front panel.
Applies to: VD2-320 to VD2-1080
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2 installation manual, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.