Viessmann · Boiler troubleshooting
System version 3: common supply pump and low pressure manifold
What is going on
Used when the distribution manifold is in a remote location (more than 20 m / 65 ft). T1 reduces or closes the mixing valves when the minimum return temperature is not reached. The common supply pump should be sized to 110% of the total heating system flow rate.
Check in this order
- Size the common supply pump to 110% of total system flow.
- Set coding 0D 1 and 4C: 2 for the wiring diagram where heating circuit control units are not connected via LON BUS.
- Connect the contactor relay and downstream control unit so that the switch closes to signal close mixing valves.
- Set coding 4d 0 for the common supply pump on plug sL.
- Check the connection diagram on site before commissioning.
Applies to: Vitorond 200 VD2, system version 3
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 13-14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.