Viessmann · Boiler troubleshooting

System version 3: common supply pump and low pressure manifold

Vitotronic 100 GC1Vitocontrol-S VD2/CT3/CM2

What is going on

Used when the distribution manifold is in a remote location (more than 20 m / 65 ft). T1 reduces or closes the mixing valves when the minimum return temperature is not reached. The common supply pump should be sized to 110% of the total heating system flow rate.

Check in this order

  1. Size the common supply pump to 110% of total system flow.
  2. Set coding 0D 1 and 4C: 2 for the wiring diagram where heating circuit control units are not connected via LON BUS.
  3. Connect the contactor relay and downstream control unit so that the switch closes to signal close mixing valves.
  4. Set coding 4d 0 for the common supply pump on plug sL.
  5. Check the connection diagram on site before commissioning.

Applies to: Vitorond 200 VD2, system version 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 13-14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.