Adjust the fixed high limit to 99°C / 210°F

Vitotronic 300

What is going on

The fixed high limit leaves the factory at 110°C / 230°F. It is required to be set to 99°C / 210°F for the Vitocrossal 300. Once set to 99°C / 210°F it cannot be reset to 110°C / 230°F. If set to 99°C / 210°F, do not set the adjustable high limit above 75°C / 167°F.

Check in this order

  1. Disconnect power to the control and the burner.
  2. Unclip the fuse box and swing it upwards.
  3. Turn the slotted screw on the rear of the fixed high limit until the slot points to 99°C / 210°F.
  4. Refit the fuse box.

Applies to: Vitocrossal 300 and condensing boilers as listed in the limit table

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.