Checking the ignition and ionization electrodes

Vitocrossal 300 CA3B Dual Fuel

What is going on

Inspect and replace the electrodes after removing the burner plate.

Likely causes

  • Electrode damage
  • Electrode gap out of specification

Check in this order

  1. Remove the burner plate to access the electrode block.
  2. Check the ignition and ionization electrodes for damage and confirm they sit at the correct distance from the burner tube.
  3. Replace electrodes if needed.
  4. Reinstall the electrode block in reverse order using new gaskets.
  5. Tighten to 4.4 lb.ft (6 Nm).

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.