Weil-McLain · Boiler troubleshooting

Check the burner flame

SVF 500/600 Series 1

What is going on

Visual flame check at high and low fire, with burner cleaning if the flame is poor.

Check in this order

  1. Look at the burner flame through the observation window at high and low fire (see pages 98-99).
  2. If the flame is poor, check combustion values. If combustion is properly set, turn the boiler off and let it cool.
  3. Remove the burner and clean it with a vacuum or water flush. Do not rub or scrape the fiber mesh when vacuuming.
  4. Let a water-flushed burner dry completely before reinstalling.
  5. Replace the burner gasket when the burner is removed.
  6. Restart the boiler and check the flame again at high and low fire.
  7. If combustion still cannot be set properly, order a replacement burner.

Applies to: SVF 500/600 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 boiler manual, p. 115. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.