Weil-McLain · Boiler troubleshooting
System Type B, Application B1: boiler direct piped – design requirements
What is going on
Use primary/secondary piping for the ECO HP. If the boiler runs at the same time as the heat pump, the boiler must be downstream of the ECO HP to prevent high return temperatures from shutting the heat pump down. Zone circulators must be sized for the required flow. Heat pump circulator is in the manifold. All zones should run safely at supply temperatures up to 149°F, or use mixing valves to bring zone temperatures down. The boiler accepts one priority/reset curve. A single boiler target temperature can replace the reset curve, and ECO Calc should be used to decide which suits the system. Additional zones can be added with additional zone panels.
Check in this order
- Pipe the heat pump primary/secondary.
- Place the boiler downstream of the ECO HP if both run together.
- Size zone circulators for the required flow.
- Confirm all zones can run at supply temperatures up to 149°F, or add mixing valves.
- Decide between the boiler reset curve and a single boiler target temperature using ECO Calc.
- Check that the DHW supply temperature is sufficient when the reset curve is enabled.
Applies to: System Type B, Application B1
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump – Application Guide, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.