Viessmann · Boiler troubleshooting
Install the safety header
What is going on
Build the safety header with the pressure relief valve, low water cutoff, automatic air vent and temperature/pressure gauge on the boiler outlet.
Check in this order
- Fit the hex bushing and the air vent with shut-off base.
- Install the pressure relief valve rated 75 psi, or an alternate valve matched to the operating pressure.
- Install the low water cutoff and the temperature/pressure gauge.
- Use the reducer and nipple sized for the model from the connection table.
Applies to: All Vitocrossal 300 CA3B Dual Fuel models
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.