Viessmann · Boiler troubleshooting

Install and check DHW tank temperature sensor

Vitocontrol-S VD2/CT3/CM2Vitotronic 100

What is going on

The sensor measures DHW tank temperature. Leave it unconnected on systems without DHW heating.

Check in this order

  1. Install the DHW tank sensor following the domestic hot water tank instructions.
  2. On DHW tanks of other makes, press the sensor against the sensor well with a suitable device.
  3. Make sure the maximum allowed DHW temperature is not exceeded; add a suitable safety device if needed.
  4. Disconnect plug in the boiler control terminal compartment.
  5. Measure sensor resistance at plug terminals 1 and 2 and compare with the tank temperature.
  6. If the value differs significantly, check installation and replace the sensor if needed.

Applies to: DHW tank temperature sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocontrol-S VD2/CT3/CM2 installation manual, p. 81. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.