Display blank and no boiler components running

ECO Tec Series 3

What is going on

The control is not getting 120 VAC power.

Likely causes

  • Service switch or breaker off.
  • No 120 VAC at the service switch or at J1.
  • Blown 4 A line voltage fuse.

Check in this order

  1. Confirm the service switch and circuit breaker are on.
  2. Check for 120 VAC at the service switch; correct the supply if none.
  3. Check for 120 VAC at the line voltage terminal block at J1 on the circuit board and correct wiring.
  4. Inspect the 4 A fuse and replace it with the Parts section part if necessary.
  5. If it blows again, recheck wiring per the diagrams.

Applies to: ECO Tec Series 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 163. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.