Display blank and no boiler components running
What is going on
The control is not getting 120 VAC power.
Likely causes
- Service switch or breaker off.
- No 120 VAC at the service switch or at J1.
- Blown 4 A line voltage fuse.
Check in this order
- Confirm the service switch and circuit breaker are on.
- Check for 120 VAC at the service switch; correct the supply if none.
- Check for 120 VAC at the line voltage terminal block at J1 on the circuit board and correct wiring.
- Inspect the 4 A fuse and replace it with the Parts section part if necessary.
- If it blows again, recheck wiring per the diagrams.
Applies to: ECO Tec Series 3
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 163. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.