Viessmann · Boiler troubleshooting

System layout 1: one heating circuit

Vitodens 100-W WB1B

What is going on

Basic layout with the boiler and one heating circuit. Heating circuit should be designed for 30 to 40 F (16.7 to 22.2 C) rise. For a lower design rise, use layout 3 or 4.

Check in this order

  1. Fit an air vent and pressure relief valve on the system.
  2. Fit the heating circuit pump and expansion tank as shown.
  3. Fit a pressure activated by-pass if components in the heating circuit can isolate the pump flow.
  4. Use a low-loss header if flow is below 1.7 GPM (400 L/h) or above 6.2 GPM (1400 L/h).

Applies to: Vitodens 100-W WB1B 26 and 35

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W, WB1B CombiPlus Installation & Service Instructions, p. 38. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.