Zone valve zoning with optional DHW piping (primary/secondary)
What is going on
A primary/secondary boiler loop keeps the boiler circulator head off the zone valves and gives the boiler enough flow.
Check in this order
- Install a system circulator sized for the required flow and head.
- Install the flow/check valve on the boiler outlet to prevent gravity circulation during DHW heating.
- Size all boiler loop piping at least to the minimum shown in the pipe sizing table.
- Wire zone valve end switches to a Space Heating Priority input (default Priority 2). Use isolation relays for 3-wire end switches.
- Use the Weil-McLain WMZV zone valve controller for more than three zones.
- For an indirect DHW tank, pipe it from the near-boiler piping to the tank boiler connections. A DHW zone is only used if no DHW tank is already on the boiler.
Applies to: Zone valve systems with optional DHW
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit 550/750 Series 3 boiler manual, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.