Zone valve zoning with optional DHW piping (primary/secondary)

SlimFit Series 3 Commercial

What is going on

A primary/secondary boiler loop keeps the boiler circulator head off the zone valves and gives the boiler enough flow.

Check in this order

  1. Install a system circulator sized for the required flow and head.
  2. Install the flow/check valve on the boiler outlet to prevent gravity circulation during DHW heating.
  3. Size all boiler loop piping at least to the minimum shown in the pipe sizing table.
  4. Wire zone valve end switches to a Space Heating Priority input (default Priority 2). Use isolation relays for 3-wire end switches.
  5. Use the Weil-McLain WMZV zone valve controller for more than three zones.
  6. For an indirect DHW tank, pipe it from the near-boiler piping to the tank boiler connections. A DHW zone is only used if no DHW tank is already on the boiler.

Applies to: Zone valve systems with optional DHW

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit 550/750 Series 3 boiler manual, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.