Burner does not start or starts intermittently (red fault LED flashes)

Vitotronic 100

What is going on

The burner does not light, or it cycles on and off with the red fault LED flashing.

Likely causes

  • Burner is not electrically connected
  • Fixed high limit (FHL) has tripped

Check in this order

  1. Make sure the 7-pole plug-in connection to the burner and/or power venter is fully connected.
  2. Check the fixed high limit. If it has tripped, reset it as described in the reset tip.
  3. Check that the control does not show a continuous burner call with the override switch on.

Applies to: Vitotronic 100 KW10B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 KW10B operating manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.