Category II (negative pressure) vent requirements

SlimFit Series 2

What is going on

SlimFit boilers can be installed as Category II with a designed vent system. The vent must hold negative pressure, and flue temperature must stay under the shutdown limit.

Likely causes

  • Positive pressure in the vent causing flue gas spillage and carbon monoxide
  • Flue gas over 216 F causing the boiler to shut down and recycle

Check in this order

  1. Use a professionally designed and engineered vent system per the local authority having jurisdiction.
  2. Use vertical vent only and do not install into an existing common vent.
  3. Take combustion air from the boiler room and follow the direct exhaust opening rules.
  4. Use a 10 in SlimFit Vent/Air adapter for the Category II vent connection.
  5. Install a 3 ft straight run of 10 in pipe directly after the adapter before any change in diameter or direction.
  6. Check that the vent pressure just after the boiler stays within the Table 1 negative pressure range at all firing rates.
  7. Keep flue gas under 216 F. Typically flue gas runs within 20 F of return water temperature; use the lowest expected return temperature for calculations.
  8. Install a carbon monoxide detector in the boiler room and wire it to the same circuit as the boiler.

Applies to: SlimFit SF1000, SF1500, SF2000 in Category II configuration

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit 1000-2000 Series 2 boiler manual, p. 27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.