Viessmann · Boiler troubleshooting

Limit maximum heating input

Vitodens 100-W, WB1B

What is going on

Heating input can be capped through the modulation range. This does not affect domestic hot water heating.

Check in this order

  1. Start up the boiler.
  2. Turn selector dial tr clockwise to U Reset, then back to the middle range within 2 seconds and on to position 6 to enter high-fire test. SERV, water temperature, five flashing bars and A show.
  3. With selector dial tr, choose a value from 1 to 6 for the required percentage of rated input. For example, position 1 shows one flashing bar and reduces input to 40% of max.
  4. Turn the water temperature selector dial clockwise within 2 seconds and back into the operating range. The icon flashes briefly to confirm the setting was accepted.
  5. Press the ON/OFF switch and start the boiler. The maximum input is now set.

Applies to: Vitodens 100-W, WB1B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.