Check and clean condensate trap and drain
What is going on
A blocked condensate drain makes condensate build up in the bottom of the boiler and causes a burner shut-down with a fault message.
Likely causes
- Condensate does not drain freely
- Debris in the condensate trap
- Drain pipe connected to another appliance such as a water softener backwash line
Check in this order
- Remove the retaining clip from the condensate trap and set it aside.
- Disconnect the flexible discharge tubing from the condensate trap.
- Remove the condensate trap from the boiler.
- Clean out debris and refill the trap with water.
- Reinstall the trap and secure it with the retaining clip.
- Reconnect the flexible discharge tubing to the trap.
- Confirm the drain has an air gap and is vented between the trap and any neutralization unit.
- Do not connect other drains, such as a water softener backwash pipe, to the condensate drain.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB service instructions, p. 26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.