Viessmann · Boiler troubleshooting
Connect the Vitotronic control and run its cables
What is going on
Connect the Vitotronic plug-in cable to the burner and route all sensor and power cables inside the boiler without touching the heat exchanger.
Check in this order
- Run the Vitotronic plug-in connector cable down behind the boiler front panel and out through the bottom.
- Connect the female plug on the burner to the male plug on the Vitotronic.
- Remove the cover plate, top back panel and front panel to mount the control console on the boiler.
- Fasten the console with the two screws.
- Push the high limit sensor and boiler temperature sensor 3 behind the front panel into the sensor wells as far as they go.
- Route power and 120 VAC cables through the back opening, and low voltage sensor cables through the cable opening.
- Coil excess cable and tuck it between the side panel and insulation, then tighten the strain reliefs.
Applies to: Vitotronic control on Vitorond 100 VR1
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100, VR1 Installation and Service Instructions, p. 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.