Inspect and fill the condensate trap
What is going on
The condensate trap must stay filled with water during operation. An empty trap lets flue gas out of the condensate drain.
Likely causes
- Trap not filled at startup
- Empty trap during operation allows flue gas emission
Check in this order
- Inspect the condensate drain line, PVC fittings and trap (see p. 61).
- Remove the test port cap from the vent adapter.
- Pour one cup of clean water into the test port.
- Confirm the trap is full of water.
- Reinstall the test port cap on the vent adapter.
Applies to: SVF 500/600 Series 1
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 95. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.