Inspect and fill the condensate trap

SVF 500/600 Series 1

What is going on

The condensate trap must stay filled with water during operation. An empty trap lets flue gas out of the condensate drain.

Likely causes

  • Trap not filled at startup
  • Empty trap during operation allows flue gas emission

Check in this order

  1. Inspect the condensate drain line, PVC fittings and trap (see p. 61).
  2. Remove the test port cap from the vent adapter.
  3. Pour one cup of clean water into the test port.
  4. Confirm the trap is full of water.
  5. Reinstall the test port cap on the vent adapter.

Applies to: SVF 500/600 Series 1

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 95. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.