Viessmann · Boiler troubleshooting

CSD-1 fixed high limit fault simulation #1 (pump removed)

Vitodens 200-W B2HB

What is going on

Test of the fixed high limit switch, required where CSD-1 applies. Viessmann is not responsible for damage caused by overheating during this test.

Check in this order

  1. Confirm the boiler and boiler pump are in normal operating condition.
  2. Remove the cover from the back of the boiler control to reach the control plugs.
  3. In the extended menu, select Test mode, then flue gas test ON, and press OK.
  4. Wait for the burner to ignite and go into high fire.
  5. Once the burner ignites, unplug the boiler pump from the control board.
  6. Watch the boiler temperature rise and the burner shut off.
  7. Confirm the temperature continues to rise to 210°F (99°C), where the high limit trips and generates an F2 fault.
  8. If the limit is not reached, wait two minutes after the burner shuts off, then energize the pump for no more than 1 second by plugging it in. Repeat as needed.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199 with boiler pump plug at control board

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB installation instructions, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.