Gas valve leakage test
What is going on
Test each gas valve solenoid separately. Do not connect a manometer to the manual or automatic gas valve, because the blower vacuum can pull fluid into the gas line and damage the valves.
Check in this order
- Refer to the gas valve manufacturer's test procedure.
- Go to the Valve Test screen on the control.
- Select Open Gas Valve 1 and press enter/save.
- Give a call for heat. The boiler will only open gas valve 1. Test at the tapping P on the valve body.
- End the call for heat once valve 1 has opened.
- Repeat with Open Gas Valve 2, testing at the manual gas valve side tapping.
- Press back to exit the Gas Valve Test screen. Both valves then open on any call for heat.
Applies to: SlimFit Series 2 gas valves
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 83. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.