Viessmann · Boiler troubleshooting

CSD-1 fixed high limit fault simulation #2 (flow switch jumpered)

Vitodens 200-W B2HB

What is going on

Alternate high limit test with the boiler valve closed and the flow switch bypassed. Viessmann is not responsible for damage caused by overheating during this test.

Check in this order

  1. Close the boiler valve.
  2. Jumper across the flow switch.
  3. Run the boiler at high fire. It shuts down through the coding card, but the temperature should keep rising until the fixed high limit trips.
  4. When the fixed high limit trips, slowly open the boiler valve to cool the boiler down.
  5. On B2TB models only, set coding address 06 to maximum to force the shutdown.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB installation instructions, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.