Viessmann · Boiler troubleshooting

Fill the condensate siphon with water

Vitodens 222-F

What is going on

The condensate siphon must be filled before start-up so exhaust gases cannot escape through the drain.

Check in this order

  1. Pivot the control unit forward.
  2. Pull retaining clip A off.
  3. Pull filler pipe B upwards.
  4. Pull off trap C downwards.
  5. Fill the siphon with water and reassemble.
  6. Check that the condensate pipe is connected correctly to the siphon and heat exchanger.
  7. Refit the cover panel and secure the control unit back in operating position.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 222-F B2TB service instructions, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.