Viessmann · Boiler troubleshooting

Detaching the upper burner section

Vitocrossal 300 CA3B Dual Fuel

What is going on

Removing the burner needs a lifting mechanism. Refer to the lifting device instructions and the service instructions when refitting.

Check in this order

  1. Disconnect the burner gas line.
  2. Disconnect the connector from the burner control unit.
  3. Pull off the ignition electrode connectors.
  4. Remove the 2 screws on the ignition electrode block and lift the block up to remove it.
  5. Remove the 6 nuts.
  6. Remove the burner.
  7. Attach lifting mechanism chains at the 3 marked points on the upper burner section frame.
  8. Lift the upper burner section with the lifting mechanism and set it aside.

Applies to: CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation instructions, p. 13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.