Viessmann · Boiler troubleshooting

Gas line connection and purge

Vitocrossal 200 CI2

What is going on

Connect and purge the gas supply to the burner gas valve before commissioning.

Check in this order

  1. Connect the gas pipe to the gas valve.
  2. Leak test the gas pipe connection with an approved method.
  3. Purge the gas line safely using an approved purge burner.
  4. Do not exceed the test pressure, as high test pressure can damage the burner and gas fittings.
  5. Do not vent gas piping above the combustion chamber of the boiler.

Applies to: Vitocrossal 200 CI2 399 to 2000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 installation manual, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.