Expansion tank check

Ultra Series 4

What is going on

Check the expansion tank when the relief valve weeps often or the pressure rises too high on heat-up.

Likely causes

  • Closed-type tank waterlogged
  • Diaphragm or bladder tank undersized or membrane damaged
  • Automatic air vents used with a closed-type tank

Check in this order

  1. Identify tank type open, closed (air cushion) or diaphragm/bladder.
  2. Open type confirm it is above the highest radiator or baseboard and the gauge glass and overflow are working.
  3. Closed type confirm a tank fitting such as B&G Tank-Trol or Taco Taco-Trol is installed. Do not use automatic air vents with closed-type tanks.
  4. If the relief valve weeps often on a closed tank, check the fill level. If correct, check tank size against manufacturer data and replace with a larger tank if needed.
  5. Diaphragm or bladder type check tank size for the system. Add tanks if too small.
  6. If size is adequate, remove the tank and check charge pressure (usually 12 psig residential). If it will not hold pressure, the membrane is damaged. Replace the tank.
  7. Systems with diaphragm or bladder tanks need at least one automatic air vent, preferably on top of an air eliminator.

Applies to: Ultra Series 4 boilers, hydronic system

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 111. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.