Viessmann · Boiler troubleshooting

Fixed high limit test #1 (boiler pump disconnected)

Vitodens 200-W B2HA

What is going on

CSD-1 field test of the fixed high limit using the boiler pump. Manufacturer disclaims damage from overheating during this test.

Check in this order

  1. Confirm the boiler and boiler pump are in normal operating condition.
  2. Remove the back cover of the boiler control to reach the control plugs.
  3. In the extended menu, select Test mode, then flue gas test ON, and press OK.
  4. Wait for the burner to ignite and go to high fire.
  5. Once the burner ignites, carefully unplug the boiler pump plug from the control board.
  6. Watch the boiler temperature rise and the burner shut off.
  7. Confirm the boiler temperature keeps rising until the manual reset high limit trips at about 210°F (99°C), giving an F2 fault.
  8. If the limit is not reached, wait two minutes after burner shutoff, then plug the pump in for a maximum of 1 second. Repeat as needed.

Applies to: Vitodens 200-W B2HA 45, 60 (boiler sizes with boiler pump plug)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.