Fixed high limit test #1 (boiler pump disconnected)
What is going on
CSD-1 field test of the fixed high limit using the boiler pump. Manufacturer disclaims damage from overheating during this test.
Check in this order
- Confirm the boiler and boiler pump are in normal operating condition.
- Remove the back cover of the boiler control to reach the control plugs.
- In the extended menu, select Test mode, then flue gas test ON, and press OK.
- Wait for the burner to ignite and go to high fire.
- Once the burner ignites, carefully unplug the boiler pump plug from the control board.
- Watch the boiler temperature rise and the burner shut off.
- Confirm the boiler temperature keeps rising until the manual reset high limit trips at about 210°F (99°C), giving an F2 fault.
- If the limit is not reached, wait two minutes after burner shutoff, then plug the pump in for a maximum of 1 second. Repeat as needed.
Applies to: Vitodens 200-W B2HA 45, 60 (boiler sizes with boiler pump plug)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.