Viessmann · Boiler troubleshooting
Checking the boiler temperature sensor (dual sensor)
What is going on
Resistance check of the dual supply temperature sensor against the temperature curve.
Check in this order
- Check the leads and plugs of the supply temperature sensors.
- Disconnect the leads from the supply temperature sensors.
- Check the sensor resistance, noting the position of guide lug B.
- Sensor 1 check connections 1 and 3.
- Sensor 2 check connections 2 and 4.
- Compare the resistances with the value for the current temperature on the curve.
- If the deviation is severe (over 10%), replace the dual sensor.
- Drain the heating water side before replacing the sensor.
Applies to: Dual boiler supply temperature sensor
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 100-W B1HE/B1KE installation/service manual, p. 82. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.