Checking the boiler temperature sensor (dual sensor)

Vitodens 100-W B1HE/B1KE

What is going on

Resistance check of the dual supply temperature sensor against the temperature curve.

Check in this order

  1. Check the leads and plugs of the supply temperature sensors.
  2. Disconnect the leads from the supply temperature sensors.
  3. Check the sensor resistance, noting the position of guide lug B.
  4. Sensor 1 check connections 1 and 3.
  5. Sensor 2 check connections 2 and 4.
  6. Compare the resistances with the value for the current temperature on the curve.
  7. If the deviation is severe (over 10%), replace the dual sensor.
  8. Drain the heating water side before replacing the sensor.

Applies to: Dual boiler supply temperature sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W B1HE/B1KE installation/service manual, p. 82. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.