Viessmann · Boiler troubleshooting

Clean heat exchanger, flue gas collar and chimney connection

Vitorond 200 VD2A

What is going on

Remove combustion residue from the heat exchanger, combustion chamber, flue collar and chimney connection. Check the gaskets and insulation at the same time.

Likely causes

  • Combustion residue builds up in the flue passages over time.

Check in this order

  1. Clean flue gas passages and the combustion chamber with the supplied brush.
  2. Clean tight spaces between the ribs with the smaller brush.
  3. Vacuum out combustion residue.
  4. Remove residue from the chimney connection and flue collar through the clean-out openings at the rear of the boiler.
  5. Check all gaskets and sealant ropes and replace any that are worn.
  6. Check the insulation of the combustion chamber door and replace it if worn.
  7. On VD2A-125 to VD2A-195, push the turbulators fully into the second flue passages.
  8. Tighten the combustion chamber door bolts in a cross pattern.
  9. If a gas power burner is used, reconnect the gas train and run leak detection.
  10. Refit the clean-out covers.

Applies to: Vitorond 200 VD2A boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2A service instructions, p. 11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.