Viessmann · Boiler troubleshooting

Check and clean ignition and ionisation electrodes

Vitodens 100-W, WB1B

What is going on

Check electrode wear, contamination and clearances.

Likely causes

  • Worn, contaminated or warped electrodes
  • Incorrect electrode clearance

Check in this order

  1. Check the ignition and ionisation electrodes for wear, contamination or warping.
  2. Clean the electrodes with a small brush or emery paper.
  3. Check the clearances. If they are wrong or the electrodes are damaged, replace the electrode block and gasket and align the new parts.
  4. Tighten the electrode fastening screws to 3.5 Nm (31 lb.in.) with a calibrated torque wrench.
  5. Refit the grounding wire.

Applies to: Vitodens 100-W, WB1B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 69. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.