Viessmann · Boiler troubleshooting
Check and clean ignition and ionisation electrodes
What is going on
Check electrode wear, contamination and clearances.
Likely causes
- Worn, contaminated or warped electrodes
- Incorrect electrode clearance
Check in this order
- Check the ignition and ionisation electrodes for wear, contamination or warping.
- Clean the electrodes with a small brush or emery paper.
- Check the clearances. If they are wrong or the electrodes are damaged, replace the electrode block and gasket and align the new parts.
- Tighten the electrode fastening screws to 3.5 Nm (31 lb.in.) with a calibrated torque wrench.
- Refit the grounding wire.
Applies to: Vitodens 100-W, WB1B
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 69. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.